What Are The Causes And Treatment Methods Of Insufficient Ignition Capacity Of The Burner? How Should We Maintain It On Weekdays?
What Are The Causes And Treatment Methods Of Insufficient Ignition Capacity Of The Burner? How Should We Maintain It On Weekdays?
1. The air valve of the burner is opened too large or the chimney baffle is opened too large, resulting in too much air entering the furnace and the burner not being easy to ignite.
The treatment method is to reduce the opening of the air valve of the burner and the opening of the chimney baffle, and then adjust the air valve and baffle to the appropriate opening.
2. When the fuel oil force is greater than the atomizing steam pressure, the burner is not easy to ignite
The treatment method is to adjust the fuel pressure to about 98kPa less than the atomizing steam pressure.
3. Routine maintenance
1) Keep each surface clean at all times.
2) When the equipment is stopped, each rotation of the quick opening blind plate (flange cover) shall be lubricated timely as required, and the lead screw of the opening and closing parts shall be coated with grease. Grease other parts as much as possible. For parts that cannot be greased, 10 # or 20 # engine oil can be injected.
4. Maintenance during operation
1) It is recommended that the operator be responsible for the daily maintenance of the equipment.
2) Always keep the equipment surface clean.
3) Monitor the reading of the differential pressure gauge at any time. When the differential pressure reaches 0.02Mpa, wash the filter element.
5. Inspection cycle
1) The regular inspection of this equipment must be carried out in strict accordance with the relevant provisions in Chapter VI of the Specifications.
2) Carry out a comprehensive inspection of the equipment at least once a year. Although the measurement of the equipment wall thickness shall be conducted once every two years, the pressure welds of the equipment shall be subject to non-destructive testing. All tests, The test results shall be recorded in the technical archives of the equipment.
3) No maintenance is allowed when there is pressure inside the equipment. Maintenance under special circumstances. Article 122 must be strictly observed.
6. Maintenance during equipment parking
1) When the equipment is parked, the liquid in the equipment shall be drained.
2) Close all valves.
3) Thoroughly clean the equipment surface.
4) All rotating parts shall be coated with anti-grease.
5) Cover all equipment with canvas to prevent dirt from depositing on the equipment’s surface.